Home      |       Company Profile     |      Products      |      Clients      |       Quality Policy      |       Contact Us      |       Enquiry
What We Do
 
Manufacture prefabricated Puf Panels
Design the telecom shelters
Supply Puf Panels
Products
Puf Panel
Telecom Shelter / Sandwich Panel
Insulated Panel for Roofing & Walling
Cold Storage & Cold Chain Solution
Puf Panel for Defence
Advantages of Puf Panels
Puf Pipe Sections & Puf Slabs 
Fire Protection & Cable Coating

Telecom Shelter

Specifications
We can comply any specifications as per the customer requirement, below are some general specifications of our present production:
  • 60, 80, 100mm puf panels
  • Outer cladding of 0.6mm, 0.8mm or 1mm thickness
  • Puf density 40kg/m3 and thermal conductivity<0.023w/mDegk
  • Base frame designed bolted beam channel grid to withstand 3500kg/sq.mt. Uniformally
  • Modular wall and roof panels to withstand 200 kmph wind load conditions
  • Self standing, self supporting galvanised steel structure
  • Projected roof of 150mm on all sides for rain protection
  • Mortice lock of stainless steel hinges
  • Floor internal skin with 19mm marine grade ply, fire retardant, fungus proof, high anti static, anti abrasive board
  • Dimensional stability - 75 to 125 degC
  • Roof loading capacity 250 kg/sq.m.
  • Torque groove configuration with inbuilt unpickable eccentric camlocks
  • Water proofing to the joints of the ceiling panels

Typical Thermal and Load Characteristics of Maxfaith Panel

Thickness

mm

60

80

100

120

150

200

"U" Values

W/m2 0C

0.36

0.26

0.21

0.19

0.14

0.11

Panel Weight

kg/m2

11.25

12.05

12.85

13.65

14.85

16.85

.

Properties of Polyurethane Foam (CFC FREE)

Density

40 +/-2 kg/m3

Compressive Strength at 10% deformation

2.1 kg/cm2

Tensile Strength

3.7 kg/cm2

Bending Strength

4.0 kg/cm2

Adhension Strength (Foam to Steel)

2.9 kg/cm2

Dimensional Stability (48 hours) at -25 0C

0.1%

-38 0C & 90% RH

0.1%

+100 0C

0.4%

Closed Cell Content

90-95%

Temperature Range

-180 0C to +95 0C

Thermal Conductivity at 0 0C (design value 0.020 k-cal/m-hr/0 C or 0.023 W/m-K)

0.018 k-cal/m-hr/0C

Fire Resistance Horizontal Extent of burn BS 4735

< 125 mm

Self Extinguishing ASTM D 1692 (fire retarded foam chemicals)

passes

Water absorption

0.2 % volume at 100 % RH

Vapour Permeability (at 90 % RH & 30 0C)

0.08 / 0.12 gms/hr m2

BACK / NEXT
.
 